Specifications
				
					Input
- Input 115VAC 60Hz, 3.5A.
 - Input fuse rated @ 3.5A/250V.
 
Output
- 12VDC or 24VDC selectable output. Burglar Alarm Applications (UL 603):
 - 12VDC = 10VDC-13.2VDC.
 - 24VDC = 20VDC-26.4VDC.
 - 2.5A total supply current.
 - Filtered and electronically regulated output.
 - Short circuit and thermal overload protection.
 
Battery Charging
- Built-in charger for sealed lead acid or gel type batteries.
 - Maximum charge current: 0.7A.
 - Automatic switch over to stand-by battery when AC fails.
 - Zero voltage drop when switched over to battery backup.
 - (Batteries are sold separately).
 
Supervision
- AC fail supervision (form "C" contacts).
 - Notification trigger is selectable for 30 seconds (factory set) or 6 hours.
 - Low battery supervision (form "C" contacts).
 - Battery presence supervision (form "C" contacts).
 
Visual Indicators
- AC input, DC output and Battery LED indicators.
 
Electrical
Temperature:
- Operating: 0° C to 49° C (32° F to 120° F).
 - Storage: - 20° C to 70° C ( - 4° F to 158° F).
 
    
- Relative Humidity: 85% +/-5%.
 
               
BTU/Hr. (approx.):
- 12VDC: 17 BTU/Hr.
 - 24VDC: 32 BTU/Hr.
 
   
- System AC input VA requirement: 402.5VA.
 
				 
					 
		
			
												
				Dimensions & Weight
				
					
											Dimensions (approximate):
						
							- 4.5"W x 7.1"L x 1.44"H (114 mm W x 180 mm L x 37 mm H).
 
						
										
					
					Weights (approximate):
						
							- Product Weigtht: 0.65 Lbs. (0.29 kg).
 
							- Shipping Weigtht: 0.8 Lbs. (0.36 kg).